INTRODUCTION
1.Application
· Electric control and power supply cabinets of CNC machine tools.
· Communication equipment.
· SPC exchange.
· Measuring instruments.
2.Functions and Features
· Two separate air circulation systems can prevent dust, oil mist and moisturefrom entering the enclosure..
· Water-in temperature can be adjusted to control temperature and humidityinside the enclosure, hence protecting electrical components.
· Compact design makes it easy to install and maintain.
· With special materials and treatments, special components are corrosionresistant and tightly sealed.
· Reliable and smooth running with less noise and greater energy efficiency.
· HV electrostatic powder coating is adopted to antistatic and make the heatexchanger delicate in appearance.
· Eco-friendly (without refrigerant) and energy-saving.
· There are diferent installation methods, including wall-mounted, roof-mountedand bottom-mounted.For each installation method, there are multiplespecifications available for your choice.
Product paramter
Item/Model | MWA-05 | MWA-08 | MWA-10 | MWA-15 | |
Cooling capacity | kW | 0.5 | 0.8 | 1.0 | 1.5 |
Airflow | m³/h | 160 | 300 | 350 | 430 |
Water flow | L/min | ≥2 | ≥3 | ≥4 | ≥6 |
Water-in temperature | ºC | 1~35 | |||
Ambient temperature | ºC | 1~55 | |||
Max.supply water pressure | bar | 1~10 | |||
Power supply | V,Hz | 1/PE AC 220V 50Hz 1/PEAC 220V 60Hz |
|||
Rated power | W | 29/31 | 79/108 | 79/108 | 79/108 |
Rated current | A | 0.13/0.14 | 0.35/0.48 | 0.35/0.48 | 0.35/0.48 |
Screw connection | Female thread | G3/8" | |||
Noise | dB(A) | ≤64 | ≤68 | ≤68 | ≤68 |
Dimension W*D*H | Wall-mounted | 220*108*550 | 220*117*659 | 300*138*520 | 400*140*920 |
Roof-mounted | 220*117*720 | ||||
Bottom-mounted | 510*420*120 | ||||
Weight | Wall-mounted | 7.5 | 9 | 10 | 15 |
Roof-mounted | |||||
Bottom-mounted | 15 |
Item/Model | MWA-20 | MWA-25 | MWA-30 | |
Cooling capacity | kW | 2.0 | 2.5 | 3.0 |
Airflow | m³/h | 500 | 700 | 1000 |
Water flow | L/min | ≥8 | ≥10 | ≥12 |
Water-in temperature | ºC | 1~35 | ||
Ambient temperature | ºC | 1~55 | ||
Max.supply water pressure | bar | 1~10 | ||
Power supply | V,Hz | 1/PE AC 220V 50Hz 1/PE AC 220V 60Hz |
||
Rated power | W | 79/108 | 135/200 | 135/200 |
Rated current | A | 0.35/0.48 | 0.6/0.88 | 0.6/0.88 |
Screw connection | Female thread | G3/8" | ||
Noise | dB(A) | ≤70 | ≤70 | ≤72 |
Dimension W*D*H | Wall-mounted | 400*140*950 | 400*190*950 | 400*190*950 |
Roof-mounted | ||||
Bottom-mounted | 850*450*97 | 885*420*120 | 1300*420*120 | |
Weight | Wall-mounted | 17 | 22 | 25 |
Roof-mounted | ||||
Bottom-mounted | 15 | 26 | 35 |